We propose a state space model for electrical power systems made by independent semi-Markov components, in which restoration times can have a nonexponential distribution, thus obtaining a more realistic reliability characterization, especially regarding the outage duration distribution. We also propose a model for an energy storage unit, assuming that the storage is fully charged when it begins to deliver power. An approximate analytical evaluation based on the minimal cut sets for the outage allows to surmount the shortcomings of the Monte Carlo approach. The application of the model for an uninterruptible power supply (UPS) system shows that the autonomy of the storage plays a key role, not only for the frequency of the load point voltage failures, but also for their duration distribution.
ما برای سیستمهای قدرت مدلی با مولفههای مستقل نیمه مارکوف ارائه میدهیم که در آن زمانهای بازیابی (ترمیم) میتوانند توزیع غیرنمایی داشته باشند، در نتیجه مشخصه قابلیت اطمینان واقعیتری، به خصوص با در نظر گرفتن توزیع مدت زمان وقفه (خاموشی)، حاصل میشود. همچنین مدلی برای یک واحد ذخیره کننده انرژی ارائه میکنیم با این فرض که وقتی این واحد شروع به تحویل توان میکند کاملا شارژ شده باشد. یک ارزیابی تحلیلی تقریبی و مبتنی بر کاتستهای کمینه برای وقفه، بر نواقص روش مونته کارلو غلبه میکند. کاربرد این مدل برای سیستم منبع تغذیه بدون وقفه (UPS) نشان میدهد که مستقل بودن انرژی ذخیره شده، یک نقش مهم نه تنها برای تعداد کاستیهای ولتاژ نقطه بار ایفا میکند بلکه در توزیع دوره زمانی آنها نیز نقش دارد.